The simple structure of the thermocouple determines its extremely plastic application shape. It can be processed into different thicknesses, lengths, single or double (usually double thermocouples are used, one as a spare) according to needs. Some thermocouples, such as armored cable thermocouples, can be bent and twisted at the head to meet the different installation shape requirements of the on-site equipment when Används .
*The measurement principle of the thermocouple is the thermoelectric effect. The biggest difference between it and other sensors is that it can generate signals without adding any excitation power supply. However, it generates extremely weak electrical signals, usually only tens of millivolts. In order to prevent signal distortion, it has high requirements for the transmission of thermoelectric potential: För det första måste en dedikerad kabel (kallad kompensationskabel) användas, och kompensationskablarna för olika typer av termoelement är också olika (e-typ med nickel-krom-koppartråd, k-typ med koppar-konstantiska tråd) . för det andra, sköldbrädan för interferenssignaler är höga, och kan kakar vanligtvis användningsskytte {}}}}}}}}}}}}}}}}}}}}}})
Kallt kompensation
The cold end compensation function of thermocouples has been widely moved into DCS{{0}} Taking the INFI-90 control system as an example, all I/O cabinets are placed in an electronic room with a constant ambient temperature (generally 18℃~21℃). In this way, when performing cold end temperature compensation in the I/O terminal cabinet, a Högprecisionsmätningsvärde kan erhållas . När termoelementets kalla sluttemperatur är nollgrader celsius (kallas t 0), kompensation Bridge R 1= r 2= {{1 {}}}}}} {20 {20 {{20 {{20 {{20 {20; is balanced, the compensation voltage Uba=0, and the total potential of the temperature measurement circuit is EAB(t,t0). When the cold end temperature of the thermocouple changes, such as rising to t1, although the thermoelectric potential of the thermocouple decreases, due to the increase in the RF value of the thermistor, the compensation bridge will have a Uba voltage output, och den totala potentialen för temperaturmätningskretsen är EAB (t, t1)+uba . Endast genom att välja arbetets nuvarande värde på kompensationsbron, kompensationsspänningen UBA kan vara exakt den del av den termoelektriska potentialen EAB (t, t1) som reduceras på grund av ökningen av den kalla änden, så att den totala potentialen (T0) stabil .
The thermoelectric potential EAB (t, t0) after the above compensation enters the signal isolator, where it is isolated and transmitted to convert the millivolt signal linearly into a 1~5 volt signal (calculated based on 900℃as the full scale) and then input into the I/O card. The analog/digital conversion is performed in the I/O card and finally sent to the Kontrollkort för beräkning och kontroll .
Programvarubehandling och kontroll
Temperatursignalen som kommer in i DCS -styrarkortet är en digital signal (när den övervakas från ingenjörens arbetsstation, det visar fortfarande millivoltvärdet), som är linjärt relaterat till ingångsmillivoltspänningsvärdet, så att omvandla det till en temperatursignal är det också nödvändigt att utföra interpoleringsberäkning i en lista .}}
At the same time, in order to ensure the reliability of the entire measurement system, multiple measuring points are installed on-site for each main and important temperature measurement parameter in the control logic. For example, for the outlet temperature of the superheater, dual measuring point input is redundant measuring point input or three measuring point input, and the corresponding control logic adopts two-choice or three-choice.
According to the law of heat transfer, the speed of heat transfer depends on the thermal resistance of the heat transfer body. Therefore, the response of any temperature measurement device to the temperature field measurement is much slower than that of the flow, liquid level, and pressure signal. Besides, there is usually a protective sleeve outside the thermocouple element. Therefore, its response to temperature changes is not a step Karakteristik men nära en tröghetskaraktäristik . Av detta skäl bör vissa ledande komponenter läggas till huvudkontroll PID för temperaturkontrollen på platsen för att förhindra att temperaturen på det kontrollerade objektet är överjusterat .}
Vanliga fel och analys
De vanliga felen för termoelement manifesteras huvudsakligen enligt följande:
a. The compensation wire of the thermocouple is connected in reverse. This is mainly a problem that occurs during infrastructure construction. It is caused by the temporary carelessness of the person in charge of wiring and is a labor factor. When a thermocouple appears
B . Isoleringsskiktet i termoelementets kompensationsledning är sliten, vilket gör att signalslingan är jordad . Detta beror främst på att kompensationstråden är hård och inte installerad i Junction -lådan . när problemet, The Junction Box -höljet är upprepad och inte installerad och den kompensation som är Worned . när problemet, The Junction Box -höljet är repetedlat och den kompensation som är Worny . När problem, är det att det är svårt att repetera. av fel återspeglas i temperaturindikationen på operatörens kontrollstation, som i allmänhet är liten .
C . Kabeldragningsterminalen i kopplingsboxen har dålig kontakt . Eftersom kompensationstråden och termoelementet är båda hårda, är det svårt att dra åt ledningen under platsen för inspektion. Operatörens kontrollstation eftersom ingen indikation eller indikationsvärdet överstiger intervallet .
d . Kompensationsresistensfel . Denna typ av fel manifesteras som en långsam stigning eller fall i temperaturindikeringsvärdet efter att termoelementet är anslutet .
e. The failure rate of the thermocouple measuring the flue at the tail of the boiler is high. During the shutdown inspection, the thermocouple was removed and it was found that the head of the thermocouple, including the sheath tube, was severely worn after being washed by flue gas. After the sheath tube was changed to wear-resistant steel material, this kind av fel dold fara eliminerades .
F . Signalskyddssystemet DCS -skåpet är dåligt jordat . Denna typ av fel kan lätt orsaka att elektrisk laddning samlas på signallinjen, orsakar signaldrift eller fluktuering .} eftersom felet med detta problem är svårt att ta reda på, den vanliga behandlingsmetoden är att avbryta signallinjen och utsläpp till marken {}}}}}}}}}}}}}}}}}}} {}}}} {}}} {}}} {}} {}}}} {}}} {}}} {}}} {}}} {}} {}}}} {}}})
g . Temperaturångssignalen misslyckas efter att ha passerat genom frånkopplingen, vilket återspeglas i den onormala temperaturvärdesignalen på operatörens kontrollstation . Det är normalt efter att du har ersatt avkopplingen .}
Ovanstående är vanliga problem som uppstår under inspektioner, men när du letar efter dessa fel rekommenderas det att först använda en multimeter för att mäta ingångsspänningsvärdet på I/O-terminalskåpet för DCS, så att du snabbt kan bestämma om det är ett problem med mätningen på plats eller ett problem i DCS-avdelningen .}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}} Signaler . Om du inte kan bestämma det, lossa ledningarna och mäta dess motståndsvärde . Vanligtvis är motståndsvärdet för ett termoelement cirka 100 .}
Mätanordning för termisk motstånd
Applikationshastigheten för temperaturmätningsanordningar som använder termiska motstånd eftersom temperaturmätelement i termiska kraftverk är bara tvåa för termoelement . Vanliga inhemska termiska motstånd är ungefär 1, 000 yuan vardera, vilket är dyrare än termoelement, men har bättre egenskaper vid höga temperaturer och högre mätning än högre mätning än accuracy än att använda 3) Upptäck mätpunkter med temperaturer under 200 grader . För närvarande används det för att mäta temperaturen på generatorspolar och fläktar och kolbruk .